Buildings Services Tutor - Logo

Hydronic Balancing DIY – Step 2: Heating Load Calculation

by | Last updated: Dec 8, 2023 | 0 comments

Some of the links on my blog are affiliate links. This means that if you click on the link and buy the item, I will receive a commission at no extra cost to you. My opinion remains unaffected.

Now that you have digested the basics of hydronic balancing in the first step, let’s move on to calculating the heating load for the building and the respective rooms. Using three example calculations, I’ll show you how you can calculate your heating load in no time at all.

A frequently asked question is: How do I calculate the heating load? As is so often the case, there are several ways to calculate the heating load. I will introduce you to three simplified calculation methods that are used for the approximate determination of the heating load in existing buildings. For new buildings, a detailed heating load calculation is carried out by a specialised company using the actual building data.

Preparation for Heating Load Calculation

Before we start calculating the heating load, we compile the building data, look at the floor plans of the building and create a room list. When looking at the floor plans for the example building, it is noticeable that there were many conversions in the course of the refurbishment. The room areas in this example are therefore partially estimated.

Building Data

Given:

  • Detached house,
  • Built in 1935,
  • renovated in 2005 (façade, roof, windows, heating)
  • Climate zone: -14 °C (Outdoor design temperature)
  • Total area (heated): 99 m²
  • Room height with ceiling ground floor: 2.5 m
  • Room height with ceiling upstairs: 2.5 m

Room List

Ground floor (EG)

  • Room 1: Entrance hall, 2 exterior walls, 1 window, 1 exterior door, room surface area: 6 m²
  • Room 2: Guest WC, 1 exterior wall, 1 window, Room surface area: 1 m²
  • Room 3: Laundry room, 1 exterior wall, 1 window, Room surface area: 3.2 m²
  • Room 4: Kitchen, 1 exterior wall, 1 window, floor space: 10.2
  • Room 5: Living room, 3 exterior walls, 3 windows, 1 exterior door, room surface area: 26.5
  • Room 6: Hallway and staircase, 1 exterior wall, 1 window, Room surface area: 6.5 m²
Figure 1: Ground floor
Figure 1: Ground floor

Upper floor (OG)

  • Room 7: Bedroom, 2 exterior walls, 1 window, room surface area: 7.9 m²
  • Room 8: Bathroom, 2 exterior walls, 1 window, Room surface area: 5.7 m²
  • Room 9: Office, 2 exterior walls, 1 window, room surface area: 13.2
  • Room 10: Guest room, 2 exterior walls, 1 window, floor space: 8.6 m²
  • Room 11: Corridor and staircase, 2 exterior walls, 2 windows, room surface area: 10.2 m²
Figure 2: Upper floor
Figure 2: Upper floor

With the existing building data, we can now start to determine the heating load.

Heating Load Calculation with the Resido Heat Load App (formerly Honeywell)

One of the simplest and most efficient ways to perform an approximate calculation of the heating load in accordance with DIN EN 12831 is with the free heating load app from Resido (formerly Honeywell). The heating load app can be downloaded free of charge from the Google Playstore for Android and the Apple Apps Store for iOS. Below you will find a short video by me (in german, but you can activate automatic generated subtitles in your language) and written instructions for the app.

Note: In the following images, the texts are in German. However, I think that you can follow the procedure in the app directly.

You are currently viewing a placeholder content from YouTube. To access the actual content, click the button below. Please note that doing so will share data with third-party providers.

More Information

In the following, I would like to show you how you can determine the heating load via the app using an example room. Firstly, a new project is created in the app and the project data is entered. You are asked for the project name, the client, the order number, the outdoor design temperature and the temperature spread between the flow and return. The first room can then be created.

Heat generatorFlowReturn flowSpreadingSystem temperature
Low temperature boiler75 °C55 °C20 K75/55
Condensing boiler50 – 75 °C35 – 55 °C15 – 20 K50/35, 60/40, 75/55
Heat pump35 – 55 °C30 – 45 °C5 – 10 K35/30, 45/35, 55/45
Table 1: Example system temperatures for various heat generators

Note: For hydronic balancing, high temperature spreads of 15 to 20 Kelvin are aimed for with low-temperature and condensing boilers in order to achieve a high heat flow. Heat pumps, on the other hand, run more efficiently at low flow temperatures, so that only a low spread of between 5 and 10 Kelvin is aimed for.

Figure 3: Creating the project data in the heating load app
Figure 3: Creating the project data in the heating load app

Example Calculation with Heating Load App for the Anteroom

You can read the values I have stored in this PDF file. The first step is to enter the room data:

  • Room name: Anteroom
  • Room height: 2.5 m
  • Room temperature: 20 °C

You can assume the following room temperatures for calculating the heating load. These are stored as “standard values” in DIN EN 12831.

Room typeRoom temperature
Living rooms and bedrooms20 °C
Rooms that are used without clothing (e.g. bathrooms)24 °C
WC rooms20 °C
heated ancillary rooms outside flats (e.g. corridors and stairwells)15 °C
Table 2: Example indoor room temperatures

After entering the basic data, we start with the air exchange rate of the room and have various options here. I have opted for “normal room utilisation, tight windows” and entered the floor area of 6 m². The result is 86.7 W.

Figure 4: Entering the data for the room air change rate
Figure 4: Entering the data for the room air change rate

Next, I entered the area for the floor of the room as 6 m². This is a floor “adjacent to an unheated room” which corresponds to the structure “wooden beam/reinforced concrete ceiling, closed air space or slag fill, with impact sound”. The result is 127.5W.

Figure 5: Entering the data for the floor
Figure 5: Entering the data for the floor

The area to the ceiling/roof can be neglected for the example room, as this is adjacent to a heated room.

In the next step, I entered the external wall. This is minus the window and door areas:

(0.38m 2.43m 0.19m 0.38m 2.44m 0.725m) * 2.5m = 16.4m²

Area minus window and door: 16.4m² – 1.05m² – 1.76m² = 13.6m²

For the outer wall I chose “brick, sand-lime brick, approx. 6 – 10 cm thermal insulation”. The result is 137.6 W.

Figure 6: Entering the data for the exterior walls
Figure 6: Entering the data for the exterior walls

The window has “double glazing” and an area of:
0.9 m * 1.17 m = 1.05 m².
The result is 98.2 W.

Figure 7: Entering the data for the window area.
Figure 7: Entering the data for the window area.

For the door, I have chosen a “heavy wooden door” with an area of:
0.9 m * 1.17 m = 1.05 m².
The result is 164.6 W.

Figure 8: Entering the data for the door area.
Figure 8: Entering the data for the door area.
Figure 9: Heating load app - display of the room heating load - anteroom
Figure 9: Heating load app – display of the room heating load – anteroom

If you add up the individual values, you arrive at the room heating load \Phi_{HL,i} = 614 W. This results in a specific value of 102.6 W/m² for the 6 m² anteroom.

Even if this value appears comparatively high at first glance, it must be remembered that we have a comparatively high proportion of outdoor areas at approx. 50 % and the value is therefore quite plausible.

Summary of the Room Loads Determined by App:

Ground floor (EG)

  • Room 1: Entrance hall, 2 external walls, 1 window, 1 external door, room load: 614 W
  • Room 2: Guest WC, 1 external wall, 1 window, room load: 102 W
  • Room 3: Utility room, 1 external wall, 1 window, room load: 172 W
  • Room 4: Kitchen, 1 external wall, 1 window, room load: 539 W
  • Room 5: Living room, 3 external walls, 3 windows, 1 external door, room load: 1882 W
  • Room 6: Hallway and stairwell, 1 external wall, 1 window, room load: 371 W

Upper floor (OG)

  • Room 7: Bedroom, 2 external walls, 1 window, room load: 728 W
  • Room 8: Bathroom, 2 external walls, 1 window, room load: 652 W
  • Room 9: Office, 2 external walls, 1 window, room load: 583 W
  • Room 10: Guest room, 2 external walls, 1 window, room load: 781 W
  • Room 11: Corridor and stairwell, 2 external walls, 2 windows, room load: 922 W

Total Heating Load

Total heating load \Phi_{HL} = 7351W

Figure 10: Heating load app - display of the total heating load - example building
Figure 10: Heating load app – display of the total heating load – example building

With the help of the Honeywell heating load app, it is quite easy to determine the sum of all rooms. In the app, the room loads are always rounded down so that the total heating load is 7346 W by adding the individual values.

In the overall result, however, the decimal numbers are taken into account, so that we have a total heating load \Phi_{HL} of 7351 W . With a total heated area of 99 m², this corresponds to a specific heat requirement of 74.25 W/m² . You can read the stored data for the example building again in this PDF file .

Heating Load Calculation with the Honeywell Data Slider

Note: The Honeywell data slider is no longer in production. We therefore recommend calculating with the Resido heating load app. Nevertheless, I would still like to show you in this section how the heating load was determined using the data slider, as this data is used as the basis for further calculations. When I wrote the original series of articles, the app did not yet exist.

Figure 11: Heat load data slider from Honeywell
Figure 11: Heat load data slider from Honeywell

The Honeywell heating load data slider (Figure 11) was developed for the simplified calculation of the heating load in existing buildings. It is based on the specifications of DIN EN 12831 and a simplified calculation method developed at the Ostfalia University of Applied Sciences.

Prof Dr Dieter Wolff and his colleagues supported the development of the heat load data slider, which can be obtained free of charge from Honeywell. The package contains the data slider, instructions, a pen for setting the values (see Figure 12) and a table for entering the values.

Figure 12: Working with the heat load data slider
Figure 12: Working with the heat load data slider

Using the data slider, I will show you below how to calculate the heating load of a room. The scale indicates the range of the slide rule from which the heating load is determined. The overview of the other calculations can be seen in the completed data sheet (Figure 13).

Example Calculation Room 1: Anteroom

  • Air change: normal room utilisation, tight windows Area: 6 m² Scale 3 = 110 W
  • Door: to outside air, heavy door Area: 0.9 m * 1.96 m = 1.76 m² Scale 6a = 110 W
  • Window: on outside air, double thermal insulation glass Surface area: 0.9 m * 1.17 m = 1.05 m² Scale 7a = 100 W
  • Floor: in unheated cellar, reinforced concrete with impact sound and screed Area: 6 m² Scale 10b = 110 W
  • Wall: on outside air, outside wall with 6…12 cm thick insulation layers Area: (0.38 m 2.43 m 0.19 m 0.38 m 2.44 m 0.725 m) * 2.5 m =16.4 m² Area minus windows and door: 16.4 m² – 1.05 m² – 1.76 m² = 13.6 m² Scale 11a = 200 W

Room heating load \Phi_{HL,i} = 630 W This results in a room load of 630 W for the 6 m² anteroom, which corresponds to a specific value of 105 W/m².

At first glance , this value seems rather high for a refurbished old building . However, it must be said that, on the one hand, we have a large proportion of areas with direct contact to the outside air (approx. 50 %) and on the other hand, the heating load data slider is somewhat inaccurate for small areas. Nevertheless, determining the heating load with the data slider was a real alternative to estimating according to building age classes. The other room loads for the building are shown in Figure 13.

Figure 13: Heating load calculation with Honeywell data slider
Figure 13: Heating load calculation with Honeywell data slider

Summary of the Room Loads Determined by Data Slider:

Ground floor (EG)

  • Room 1: Entrance hall, 2 external walls, 1 window, 1 external door, room load: 630 W
  • Room 2: Guest WC, 1 external wall, 1 window, room load: 90 W
  • Room 3: Utility room, 1 external wall, 1 window, room load: 130 W
  • Room 4: Kitchen, 1 external wall, 1 window, room load: 610 W
  • Room 5: Living room, 3 external walls, 3 windows, 1 external door, room load: 1830 W
  • Room 6: Corridor and stairwell, 1 external wall, 1 window, room load: 380 W

Upper floor (OG)

  • Room 7: Bedroom, 2 external walls, 1 window, room load: 550 W
  • Room 8: Bathroom, 2 external walls, 1 window, room load: 410 W
  • Room 9: Office, 2 external walls, 1 window, room load: 990 W
  • Room 10: Guest room, 2 external walls, 1 window, room load: 670 W
  • Room 11: Corridor and stairwell, 2 external walls, 2 windows, room load: 680 W

Total Heating Load

Total heating load \Phi_{HL} = 6970 W

Using the Honeywell data slider, it was now relatively easy to determine the heating load of the individual rooms. The sum of all room loads results in a total heating load \Phi_{HL} of 6970 W, which corresponds to a specific heat requirement of 70.40 W/m² for a total heated area of 99 m².

Heating Load Calculation using the Energy Classes of Buildings

The second option for calculating the space heating load is via the specific heat requirement in watts per square metre (W/m²) according to the energy class of the building (see DeltaQ – Energy classes of buildings). These are graded as follows:

  • 130 – >200 W/m² Buildings without thermal insulation from before 1977
  • 70 – 130 W/m² Buildings according to the 1977 Thermal Insulation Ordinance
  • 60 – 100 W/m² Buildings in accordance with the 1982 Thermal Insulation Ordinance
  • 40 – 60 W/m² Buildings in accordance with the 1995 Thermal Insulation Ordinance
  • 30 – 50 W/m² Buildings according to EnEV 2002
  • 25 – 40 W/m² Low-energy house
  • 15 – 30 W/m² Ultra-low-energy house (three-litre house)

The building classes can also be further simplified as shown below:

  • 120 W/m² Old building, without special thermal insulation
  • 60 – 100 W/m² Buildings with normal thermal insulation
  • 40 – 60 W/m² New building according to thermal insulation ordinance 1995
  • 30 – 50 W/m² New building according to thermal insulation/ EnEV 2002

Determination of the Specific Heat Requirement

Estimating the specific heat requirement for a renovated old building requires some experience. Therefore, if you are unsure, you should seek the advice of a specialised company. My assumption for the example building is a specific heat requirement of Q_{spec.} = 60 – 80 W/m², which results from the following assumption:

  • The example building was built in 1935 and refurbished in 2005.
  • The façade and roof were insulated, new windows were installed and the heating system was replaced.
  • Even though the building was renovated to make it more energy efficient in 2005, there is still increased heat loss through the areas that were not renovated to make them more energy efficient, such as the cellar and doors.

With the aforementioned assumption of Q_{spec.} = 60 – 80 W/m², the following specific room heating loads result. Rooms with a large proportion of external components are rated worse than rooms with a small proportion of external components.

Ground floor (EG)

  • Room 1: Entrance hall, 2 external walls, 1 window, 1 external door, room area: 6 m² specific room heating load: 6 m² * 80 W/m² = 480 W
  • Room 2: Guest WC, 1 external wall, 1 window, room area: 1 m² specific room heating load: 1 m² * 60 W/m² = 60 W
  • Room 3: Utility room, 1 external wall, 1 window, room area: 3.2 m² specific room heating load: 3.2 m² * 60 W/m² = 192 W
  • Room 4: Kitchen, 1 external wall, 1 window, room area: 10.2 m² specific room heating load: 10.2 m² * 60 W/m² = 612 W
  • Room 5: Living room, 3 external walls, 3 windows, 1 external door, room area: 26.5 m² specific room heating load: 26.5 m² * 80 W/m² = 2120 W
  • Room 6: Corridor and stairwell, 1 external wall, 1 window, room area: 6.5 m³ Specific room heating load: 6.5 m² * 60 W/m² = 390 W

Upper floor (OG)

  • Room 7: Bedroom, 2 external walls, 1 window, room area: 7.9 m² specific room heating load: 7.9 m² * 80 W/m² = 632 W
  • Room 8: Bathroom, 2 external walls, 1 window, room area: 5.7 m² specific room heating load: 5.7 m² * 80 W/m² = 456 W
  • Room 9: Office, 2 external walls, 1 window, room area: 13.2 m² specific room heating load: 13.2 m² * 80 W/m² = 1056 W
  • Room 10: Guest room, 2 external walls, 1 window, room area: 8.6 m² specific room heating load: 8.6 m² * 80 W/m² = 688 W
  • Room 11: Corridor and stairwell, 2 external walls, 2 windows, room area: 10.2 m² specific room heating load: 10.2 m² * 60 W/m² = 636 W

Total Heating Load

specific total heating load \Phi_{HL,spec.} = 7329 W

With the help of specific values, we have succeeded in determining the specific heating load of the individual rooms. The sum of all room loads results in a specific total heating load \Phi_{HL,spec.} of 7329 W, which corresponds to a specific heat requirement of 74.03 W/m² for a total heated area of 99 m².

Conclusion

Above, three options were shown which illustrate the simplified calculation of the heating load in existing buildings. Interestingly, the deviation of the total heating loads is only 5 %. However, if we take a closer look at the space heating loads of the individual rooms, deviations of up to 30 % arise (for example: Room 1: Anteroom – 630 W to 480 W). These deviations per room are equalised across all rooms in all methods, so that the total heating loads ultimately show only a slight deviation. However, as we are trying to optimise a heating system, the heating load calculation for each room is important for comparison with the existing radiators.

Note: For more accuracy in the approximate heating load calculation, you should therefore definitely use the heating load app instead of calculating with specific values.

Initially, less additional work is required to record the data, but this can prove to be a time advantage in retrospect. In the next steps of the series “Doing hydraulic balancing yourself”, I will use the room heating loads from the calculation with the Honeywell data slider, as I have explained the function of the app at a later stage.

With the data we have now obtained, we will be able to take the next step in hydronic balancing and start recording the radiator data. If you have any questions, suggestions or criticism, please use the comments function.

Below you will find an overview of the “Hydronic Balancing DIY” series:

Overview of the series:

Related articles outside the series:

Important: Before you start with the instructions for hydronic balancing, I would like to point out that the procedures described here are based on my personal experience and my personal train of thought. Trying out and implementing the procedures described is entirely at your own risk and responsibility. I do not accept any responsibility. Furthermore, I recommend that you always have the calculated values checked by a specialised company or engineering firm. Because even if the method described here seems simple, calculation errors can always creep in.

Best regards, Martin

Further links and sources:

Resido heating load app – Google Play
Resido heating load app – Apple Store
Honeywell – Heat load data slider
TGA Fachplaner – Heat load data slider
DeltaQ – Energy classes of buildings
DeltaQ – Heating load calculation

About Me

Martin-SchlobachHi, my name is Martin and I’m a passionate engineer in the field of buildings technology. Here you can read who I am and why I write this blog.

Posts you might also like

Hydronic Balancing DIY – Step 5: Volumetric Flow Calculation

Hydronic Balancing DIY – Step 5: Volumetric Flow Calculation

[latexpage]In the fifth step of the"Hydronic Balancing DIY" series, we will calculate the volumetric flow for each radiator in the example building. In the previous steps for hydraulic balancing, we recorded all the important data and can now process it. Tip: You can...

Hydronic Balancing DIY – Underfloor Heating and Floor Warming

Hydronic Balancing DIY – Underfloor Heating and Floor Warming

This article is about the difference between underfloor heating and floor warming in the series "Hydronic Balancing DIY". As I suspected underfloor heating in the kitchen of our example building and couldn't find any documentation, I asked the manufacturer Oventrop to...

Leave a Comment:

Subscribe
Notify of
guest

This site uses Akismet to reduce spam. Learn how your comment data is processed.

0 Comments
newest
oldest most voted
Inline Feedbacks
View all comments
0
Would love your thoughts, please comment.x
()
x